iPES 6030 – CONTROL UNIT AND POWER SUPPLY FOR ELECTROMAGNETS


Installation

  • The iPES series control systems are available with IP20 protection for built-in use or in a stand-alone version with increased IP54 protection. The control system is designed for normal operating environments, in the operating temperature range -20°C to +85°C at a non-condensing maximum relative humidity of 90.
  • Before connecting the control system, it is necessary to check that the mains supply voltage corresponds to the voltage specified on the device.
  • It is necessary to connect the protective wire to the PE terminal.
  • Input AC supply voltage must be connected to terminals L1 and L2(N) – iPES control systems are designed to operate over an extremely wide range of supply voltages (110 to 230 V AC).
  • The electromagnetic clamping plates (or individual coils of the electromagnetic chuck) must be connected to the DC output voltage terminals DC OUT 1 to DC OUT 6.
  • The ENABLE IN interlock input terminals can be connected to the master device. If the interlock input is not used, the U1 and IN inputs must be shorted.
  • The terminals of the RELAY RE1 safety contact can be connected to a master device (e.g. industrial PLC,…).
  • The control box is connected to the control unit by a 10-wire shielded cable – terminals 1 to 11 of the REMOTE CONTROL connector. This conductor must be placed separately from the other (power) conductors. The cable must be protected from environmental influences and mechanical damage.

The installation of the control system must only be carried out by a person with the appropriate electrical qualifications.